Statistical analysis of operating times of high voltage SF6 circuit breakers

N. Mabunda, P. Bokoro, D. Nicolae

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

2 Citations (Scopus)

Abstract

In this paper the operating times of high voltage SF6 live tank circuit breakers are tested using standard timing tests. The time measurements obtained have proven to be adequate to the normal distribution. The hypothesis testing methodology is applied in order to determine the mean difference value between the tested phase operating times. The results obtained showed that the time difference between the operating times of the tested circuit breakers is located between -0.661 and 0.536 ms, which indicates that the operating mechanism of the breakers is still reliable and in good condition.

Original languageEnglish
Title of host publicationEEEIC 2016 - International Conference on Environment and Electrical Engineering
PublisherInstitute of Electrical and Electronics Engineers Inc.
ISBN (Electronic)9781509023196
DOIs
Publication statusPublished - 29 Aug 2016
Event16th International Conference on Environment and Electrical Engineering, EEEIC 2016 - Florence, Italy
Duration: 7 Jun 201610 Jun 2016

Publication series

NameEEEIC 2016 - International Conference on Environment and Electrical Engineering

Conference

Conference16th International Conference on Environment and Electrical Engineering, EEEIC 2016
Country/TerritoryItaly
CityFlorence
Period7/06/1610/06/16

Keywords

  • SF circuit breaker
  • hypothesis testing
  • normal distribution
  • timing test

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Renewable Energy, Sustainability and the Environment
  • Electrical and Electronic Engineering