Abstract
In this paper, a simple yet robust closed-loop identification method is proposed, and an auto-tuner is then constructed. Using the FFT, the process frequency response is first calculated from the recorded process input and output time responses to the closed-loop test. Then the process step response is constructed using the inverse FFT. A general second-order plus dead time model is thus obtained using our newly developed technique on robust identification of process transfer function from step responses. Simulation examples and real time test show its effectiveness.
Original language | English |
---|---|
Pages | 133-138 |
Number of pages | 6 |
Publication status | Published - 2000 |
Externally published | Yes |
ASJC Scopus subject areas
- Control and Systems Engineering
- Modeling and Simulation
- Computer Science Applications
- Electrical and Electronic Engineering